BICSI DCDC-002 (BICSI Data Center Design Consultant - DCDC) Certification Exam is a professional certification exam that is designed to validate the skills and knowledge of individuals who are involved in the design, implementation, and management of data centers. BICSI Data Center Design Consultant - DCDC certification is offered by the Building Industry Consulting Service International (BICSI), which is a global professional association that provides information, education, and knowledge assessment for individuals and companies in the information and communications technology (ICT) industry.
NEW QUESTION # 15
where should the telecommunications room for the operations center be located
- A. inside the computer room
- B. on another floor entirely from the operations center
- C. in an offsite location
- D. within a designated telecommunication space outside of computer rooms
Answer: D
NEW QUESTION # 16
when is a battery room required to have electrolyte spill containment and exhaust systems?
- A. when the batteries contain liquid, free-flowing electrolyte
- B. when using Lithium batteries
- C. when using Nickel Cadmium batteries
- D. when using Sealed lead-acid-batteries
- E. All of Above
Answer: A
Explanation:
Explanation
NEW QUESTION # 17
What is the recommended amount of fuel supply needing to be available to a class F2 data center?
- A. 30 hours
- B. 12 hours
- C. 36 hours
- D. 24 hours
- E. 18 hours
Answer: D
NEW QUESTION # 18
What are the minimum separation distances for electrical and telecom services pathways to maintain from their primary and redundant feeds?
- A. 20 meters (66 feet)
- B. 15 meters (49 feet)
- C. 10 meters (33 feet)
- D. 5 meters (16 feet)
Answer: A
NEW QUESTION # 19
Where is temperature typically measured in a data center HVAC system?
- A. At the CRAC unit inlet
- B. At the server rack exhaust
- C. At the server rack inlet
- D. At the CRAC unit exhaust
Answer: A
NEW QUESTION # 20
What is the acceptable dew point level in a data center according to TIA-942?
- A. 65 degrees
- B. 60 degrees
- C. 75 degrees
- D. 69.8 degrees
- E. 80 degrees
Answer: D
NEW QUESTION # 21
What is the third preference regarding electricity supply?
- A. One Circuit From Single Sub Station Fed Via Additional Path from Alternate Power Grid
- B. Two Balanced Feeds With Same Voltage Derived From A Single Distribution Station
- C. One Balanced Feeder Coordinated With Upstream Backup Feed
- D. At Least Two Circuits From Same Power Grid But Different Substations And Separate Paths
Answer: D
NEW QUESTION # 22
How many air changes an hour inside an equipment room?
- A. 0.50
- B. 1.50
- C. 1.00
- D. 2.00
- E. 0.25
Answer: E
NEW QUESTION # 23
What is the minimum separation distance for redundant utility service feeds
- A. 4 feet along entire route
- B. 22 feet along entire route
- C. 44 feet along entire route
- D. 66 Feet Along the Entire Route
Answer: D
NEW QUESTION # 24
What is the minimum slab floor to ceiling height recommended?
- A. 15feetminimmum
- B. 14feetminimum
- C. 12feetminimum
- D. 16feetminimum
Answer: A
NEW QUESTION # 25
What is typically considered the demarcation point for electrical utility at a data center?
- A. The switchboard
- B. The transformer
- C. The generator
- D. The UPS
Answer: B
Explanation:
Explanation
NEW QUESTION # 26
What kind of height clearance should data center access roads have?
- A. A Minimum clear road width and sixteen (16) ft height clearance throughout.
- B. A Minimum clear road width and six(06) ft height clearance throughout.
- C. A Minimum clear road width with fourteen (14)ft hight clearance throughout.
- D. None Of The Above.
Answer: C
NEW QUESTION # 27
What is the minimum required headroom for overhead cable tray?
- A. 6"
- B. 9"
- C. 3"
- D. 12"
Answer: A
NEW QUESTION # 28
What is the minimum raised floor height?
- A. 18"
- B. 24"
- C. 12"
- D. 6"
Answer: A
NEW QUESTION # 29
When is a battery room required to have electrolyte spill containment and exhaust systems?
- A. when the potential for outgassing hydrogen exists
- B. when the battery weight exceeds 500 pounds
- C. When corrosive fumes are detected in operation room
- D. When the ceiling suspended load capacity is below 20 pounds per square foot
Answer: A
NEW QUESTION # 30
What is the smoke development rating required for all materials hosted in a containment system?
- A. 0
- B. 1
- C. 2
- D. 3
Answer: C
NEW QUESTION # 31
What is the recommended amount of fuel supply to be available to a class F0 data center?
- A. 12 hours
- B. None - No requirements
- C. 24 hours
- D. 48 hours
Answer: B
NEW QUESTION # 32
where should printers be located
- A. in a dedicated print room with dedicated air handling system
- B. placed outdoor, away from building facilities
- C. near equipment that has active air flow to cool them down
- D. beside high traffic areas
Answer: A
NEW QUESTION # 33
What are the 2 minimum thicknesses of regular floor slabs?
- A. 6 inches and 8 inches
- B. 8 inches and 10 inches
- C. 4 inches and 6 inches
- D. 10 inches and12inches
Answer: A
NEW QUESTION # 34
......
Candidates who pass the BICSI DCDC-002 Exam are recognized as experts in data center design and management. BICSI Data Center Design Consultant - DCDC certification is highly respected by employers and is often required for professionals who work in data center design and management. DCDC-002 exam is challenging and requires a significant amount of preparation, but the rewards are well worth the effort. With a BICSI DCDC-002 certification, professionals can advance their careers and increase their earning potential in the data center industry.
To sit for the DCDC-002 exam, candidates must have at least two years of experience in the design and implementation of data centers. They must also have completed the BICSI Data Center Design course or have equivalent knowledge and experience. DCDC-002 exam is conducted in a computer-based format and consists of 100 multiple-choice questions. Candidates must score at least 70% to pass the exam and earn the DCDC certification.